MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6 General Maintenance Methods
|
No
|
No
|
Note: Overspeed valve or life jacket were not category 5 tested due to pending jack replacement.
|
3/1/2024
|
|
conversion
|
conversion
|
n/a
|
No
|
No
|
Verify if 5 year full load test was performed on life jacket, if not done, perform test.
|
10/3/2018
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
2-way communication device shall give proper location message, Responding Agent could not provide location or elevator number.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: PM/callback/repair/testing logs incomplete or missing for 2022 - 2024.
|
10/9/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: PM/callback/repair/testing logs incomplete or missing for 2022 - 2024. Violation to be certified as corrected by owner.
|
10/16/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/9/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/24/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Code compliant maintenance records shall be kept on-site.
|
10/15/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
No
|
No
|
Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time.
|
7/24/2024
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.11 - Plunger and Cylinder
|
3.18
|
No
|
No
|
Correct the plunger gripper low battery warning.
|
10/15/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. No Certificate displayed. REPEAT VIOLATION, incorrectly marked compliant.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
No
|
No
|
Display current state operating certificate.
|
10/15/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
Yes
|
No
|
Emergency lighting shall work.
|
10/9/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
Yes
|
No
|
Emergency lighting shall work. (2nd Notice)
|
6/4/2026
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP, 2 of 5 previous months in 2026 have been documented.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire service operation shall be tested monthly and a testing log shall be kept on-site.
|
10/15/2019
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire service testing must be documented monthly. No documentation for 2022 - 2024 and most of 2025.
|
10/9/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
No
|
No
|
Fire service testing must be documented monthly. No documentation for 2022 - 2024 and most of 2025. Violation to be certified as corrected by owner.
|
10/16/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.8 - Car safeties and guiding members - including roped-hydraulic elevators installed under A17.1b-1989 and later editions
|
8.11.2.1.5(j)
|
Yes
|
Yes
|
Perform Category 5 test on life jacket.
|
7/26/2018
|