ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.2.3 Guards Between Adjacent Pits
|
|
|
The pit light shall work.
|
10/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Display current state operating certificate.
|
10/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
Fire service emergency operation shall be tested monthly and a log of the testing shall be kept on-site.
|
10/30/2019
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
Code compliant maintenance records shall be kept on-site.
|
10/30/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
Emergency light and bell shall work.
|
8/19/2019
|
conversion
|
conversion
|
n/a
|
|
|
Replace expired battery in door restrictor control box.
|
11/7/2018
|
conversion
|
conversion
|
n/a
|
|
|
Verify if 5 year full load test was performed on life jacket, if not done, perform test.
|
11/7/2018
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Clean the pit.
|
7/20/2020
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator.
|
9/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Per the State of Missouri: The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals. This unit is equipped with an automatic oil recovery system.
|
9/15/2022
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
The presence of an overspeed valve has been confirmed along with an installation date of 1973. The overspeed valve shall be scheduled for a category 5 test in 2023.
|
9/15/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time.
|
7/24/2024
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
7/24/2024
|