Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No 2-way communication device shall give proper location message, Responding Agent could not provide location or elevator number.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/24/2024
MO Minimum : Elevators (I) - Pits (I)1 No No All pits shall be kept dry, clean, and free of equipment or material not relating to the operation of the elevator. 9/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Code compliant maintenance records shall be kept on-site. 10/30/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Compliant/required documentation & MCP shall be kept in equipment room (neat/organized and not on car top) including wiring diagrams, oil log, and fire service log, recorded monthly. Not present in the machine room at this time. 7/24/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Current State Operating Permit shall be displayed in the Equipment Room in a non-combustible frame. No Certificate displayed.
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate. 10/30/2019
conversion conversion conversion - reinspect Yes No Emergency light and bell shall work. 8/19/2019
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters Emergency Operation: Monthly Testing No No Fire service emergency operation shall be tested monthly and a log of the testing shall be kept on-site. 10/30/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4.1(a) On-Site Maintenance Records (MCP Records) No No Fire Service must be tested and properly documented monthly on Log Sheet located in the MCP, 2 of 5 previous months in 2026 have been documented.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection No No Per the State of Missouri: The use of oil recovery systems to return the hydraulic fluid back into the main reservoir by automatic means or by gravity feed prevents proper monitoring of the gland packing and seals. This unit is equipped with an automatic oil recovery system. 9/15/2022
conversion conversion n/a No No Replace expired battery in door restrictor control box. 11/7/2018
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.3 Guards Between Adjacent Pits No No The pit light shall work. 10/30/2019
MO Minimum : Elevators (I) - Pits (I)1 No No The pit shall be kept clean. Clean the pit. 7/20/2020
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No The presence of an overspeed valve has been confirmed along with an installation date of 1973. The overspeed valve shall be scheduled for a category 5 test in 2023. 9/15/2022
conversion conversion n/a No No Verify if 5 year full load test was performed on life jacket, if not done, perform test. 11/7/2018