conversion
|
conversion
|
n/a
|
|
|
Pit light shall work.
|
10/29/2019
|
|
conversion
|
conversion
|
n/a
|
|
|
Replace expired battery in door restrictor control box.
|
10/29/2019
|
|
conversion
|
conversion
|
n/a
|
|
|
Door closing force exceeds 30 lbs.
|
10/29/2019
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Clean the pit.
|
10/29/2019
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4.1(a) On-Site Maintenance Records (MCP Records)
|
|
|
MCP is not present in the machine room at this time.
|
8/26/2024
|
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Replace missing ceiling tiles in the machine room.
|
8/26/2024
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Pit shall be kept clean. Remove excess debris.
|
8/26/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
Category 5 testing due on the overspeed valve on or before the next annual inspection.
|
8/26/2024
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
11/7/2024
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Alarm button jams/sticks. Take corrective action as needed.
|
10/9/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: PM/callback/repair/testing logs incomplete or missing for 2022 - 2024.
|
10/9/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Fire service testing must be documented monthly. No documentation for 2022 - 2024 and most of 2025.
|
10/9/2025
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
10/9/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Remove excess debris.
|
10/9/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
|
|
Alarm button jams/sticks. Take corrective action as needed. Violation to be certified as corrected by owner.
|
10/16/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required shall be provided in the machine room. Note: PM/callback/repair/testing logs incomplete or missing for 2022 - 2024. Violation to be certified as corrected by owner.
|
10/16/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.6.11.1 Monthly Test and Log
|
|
|
Fire service testing must be documented monthly. No documentation for 2022 - 2024 and most of 2025. Violation to be certified as corrected by owner.
|
10/16/2025
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
The pit shall be kept clean. Remove excess debris. Violation to be certified as corrected by owner.
|
10/16/2025
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Auxiliary power lowering shall be operational.
|
11/7/2024
|
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(1) Minimum Standard
|
x
|
|
Battery lowering shall work. Unit has been physically disabled. Repair or replace.
|
10/9/2025
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Provide testing of Phase 1 & Phase 2 fire service. No keys available to check fire service. A set of fire service keys shall be kept on site at all times.
|
9/25/2019
|
|
A17.1-2016 : Elevators
|
1.17 - Standby power operation
|
8.6.4.19.7 (Re-Inspection)
|
x
|
|
Battery lowering device does not work per code. Where auxiliary power lowering operation is installed or altered, it shall conform to 3.26.10.
|
9/9/2022
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days)
|
x
|
|
Two-way communication device shall work with and without main power, and give proper location.
|
8/14/2023
|