Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (H) - Machine Rooms (H)8 Disconnect is obstructed by a conduit. 1/22/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Correct source of roof leak above the controller. 1/22/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency lighting shall be operational. 2/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x The emergency bell shall be operational. 2/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO state operating certificate shall be displayed in the elevator machine room.
MO Minimum : Elevators (A) - Hoistways (A)16 The top floor interlock shall have a cover.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase 2 fire service shall be operational. 10/11/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and displayed in the elevator machine room.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair or replace the light in the pit. The pit light shall be operational.
MO Minimum : Elevators (I) - Pits (I)1 The pit shall be kept clean.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x x This unit is red tagged due to the governor switch tripping too early at 190 FPM. 10/8/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The annual inspection and category 5 test still need to be completed. 10/8/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Phase II fire service does not bypass the door re-opening device. 1/22/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 x The ceiling is leaking and a tarp is covering the controller. Roof shall be repaired. 1/22/2025
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room shall be kept clean and free from non-elevator material.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars The top of the car shall be kept clean.
MO Minimum : Elevators (I) - Pits (I)1 Pit shall be kept clean and dry.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Repair or replace the light in the pit.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (H) - Machine Rooms (H)2 x The ceiling is leaking and a tarp is covering the controller. Roof shall be repaired to prevent water from damaging elevator equipment. Note: Violation not corrected at time of 1/22/25 re-inspection.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.