A17.1-2016 : Elevators 3.12 - Pipes, wiring, and ducts 8.11.3.1.3(m) junction box missing cover in the hoistway between middle and top floor. 9/28/2023
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation monthly fire service test log is not being filled out 9/28/2023
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year. 9/28/2023
conversion conversion n/a machine room fire extinguisher inspection tag is expired, need to get updated inspection on fire extinguisher 6/21/2018
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 the pit bucket is upside down, oil line is not in the bucket 9/28/2023
A17.1-1996 : Elevators 4.2 - Hoistway doors 110 missing pull straps on hoistway doors, landing #1 both sides of door, landing #B outside pull strap (110.12h) 9/28/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.5.5.2 Oil Leakage Collection Does not have oil collection bucket in the pit, provide oil collection bucket
MO Minimum : Elevators (I) - Pits (I)1 Water in the pit, provide means to prevent the accumulation of water in the pit. Pumped water out, attached sump pump didn’t work
A17.1-2016 : Elevators 4.2 - Hoistway doors 8.11.3.1.4(b) x one of the pull straps is missing on the middle landing hoistway door 8/15/2022
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone did not work, phone line is dead, provide a working phone line 6/22/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emergency phone in the elevator is not working, phone line is dead. provide working phone line to the elevator controller 8/25/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x emg. phone not working 6/1/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x the emergency phone is not working, phone line is dead 8/15/2022