MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.2 Oil Leakage Collection
|
|
|
Does not have oil collection bucket in the pit, provide oil collection bucket
|
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone did not work, phone line is dead, provide a working phone line
|
6/22/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emergency phone in the elevator is not working, phone line is dead. provide working phone line to the elevator controller
|
8/25/2020
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
emg. phone not working
|
6/1/2021
|
A17.1-2016 : Elevators
|
3.12 - Pipes, wiring, and ducts
|
8.11.3.1.3(m)
|
|
|
junction box missing cover in the hoistway between middle and top floor.
|
9/28/2023
|
conversion
|
conversion
|
n/a
|
|
|
machine room fire extinguisher inspection tag is expired, need to get updated inspection on fire extinguisher
|
6/21/2018
|
A17.1-1996 : Elevators
|
4.2 - Hoistway doors
|
110
|
|
|
missing pull straps on hoistway doors, landing #1 both sides of door, landing #B outside pull strap (110.12h)
|
9/28/2023
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters’ Emergency Operation Documentation
|
|
|
monthly fire service test log is not being filled out
|
9/28/2023
|
A17.1-2016 : Elevators
|
4.2 - Hoistway doors
|
8.11.3.1.4(b)
|
x
|
|
one of the pull straps is missing on the middle landing hoistway door
|
8/15/2022
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
The building shall post the operating certificate in the elevator equipment room, and it needs to be updated with a new copy every year.
|
9/28/2023
|
A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
the emergency phone is not working, phone line is dead
|
8/15/2022
|
A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
the pit bucket is upside down, oil line is not in the bucket
|
9/28/2023
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Water in the pit, provide means to prevent the accumulation of water in the pit. Pumped water out, attached sump pump didn’t work
|
|