Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records All the on site documentation required by A17.1 2016 - 8.6.1.2.2 shall be provided in the machine room. 2/1/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.2.2(d) On-Site Documentation (Written Procedures for Evacuation and Cleaning) A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. (This item is for notification purposes for future violation in 2022) 4/7/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting The in-car lighting fixture must be guarded. 2/28/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing The overspeed valve has an installation date of 1998. It shall be tested with the rated load on or before the next annual test. Note: Category 5 testing was originally due in 2023. The State of Missouri granted a request to delay testing to 2024 to coincide with traction elevators that need category 5 testing in 2024. 2/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x The in-car telephone shall be operational. 2/22/2024