Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No Emergency phone in car shall be answered. Re-inspection required 3/25/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Cab phone inoperative. Phone signal missing. 4/22/2019
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing No No OSV is not sealed. Perform OSV test on or before next annual inspection. 3/23/2021
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.7.9.1 No No Lighting in machine room is controlled by a timed/motion detector type switch which is prohibited by National Electrical Code NFPA 110.26D. Need to replace with standard type light switch.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current operating certificate shall be displayed in the machine room 10/28/2025