Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and post a log in the machine room 7/22/2020
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log is not being filled out monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The monthly fire service test log is not being filled out, post a monthly fire service test log in the machine room and fill it out log monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The monthly fire service test log is not being filled out since 2020, post a monthly fire service test log in the machine room and fill it out log monthly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation the monthly fire service test log in not being filled out monthly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers machine room fire extinguisher last inspection was in 2020, it is to be inspected annually
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate is to be displayed in the machine room, the most current certificate expired in 2021
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate state operating certificate in the machine room is to be updated every year, the one in the machine room is from 2017
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate is to be displayed in the machine room, the most current certificate expired in 2021
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light is burnt out, replace bulb or repair the circuit so the light works
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Pit light is burnt out, replace bulb
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) pit light is burnt out, replace bulb
MO Minimum : Elevators (I) - Pits (I)1 clean pit, oil on pit floor
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements replace broken alarm bell chicklet in the car operating panel 7/22/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone did not have a dial tone 4/12/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone did not have a dial tone, provide working phone line to the elevator controller
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Only has one working light bulb in the elevator cab ceiling, required to have at least two working light bulbs in the elevator cab ceiling
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Only has one working light bulb in the elevator cab ceiling, required to have at least two working light bulbs in the elevator cab ceiling
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)6 door reversal light ray is not working, repair or replace with working light ray door reversal device 7/22/2020