Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log Perform monthly fire service test and post a log in the machine room 8/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements replace missing car direction lantern lense 8/21/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.11.1 Firefighters' Emergency Operation & Documentation monthly fire service test log is not being filled out monthly
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log monthly fire service test log needs to be filled out monthly
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate post a copy of the state operating certificate in the machine room when received from the state
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The monthly fire service test log is not being filled out, post a monthly fire service test log in the machine room and fill it out log monthly
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Only has one working light bulb in the elevator cab ceiling, required to have at least two working light bulbs in the elevator cab ceiling
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Missing pickup roller on top landing hoistway door interlock assembly
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate The current state operating certificate is to be displayed in the machine room, the most current certificate expired in 2021, post current copy of state certificate in the machine room
MO Minimum : Elevators (S) - Fire Service 8.6.11.1 Monthly Test and Log The monthly fire service test log is not being filled out, post a monthly fire service test log in the machine room and fill it out log monthly
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Only has one working light bulb in the elevator cab ceiling, required to have at least two working light bulbs in the elevator cab ceiling
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Missing pickup roller on top landing hoistway door interlock assembly
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone did not have a dial tone, provide working phone line
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Emergency phone did not have a dial tone, provide working phone line 4/12/2024