Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall be operational. 9/2/2022
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x Battery lowering shall be operational. 4/7/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test. 5/10/2023
A17.1-1996 : Elevators 11 CSR 40-5.090 Inspection and Testing 8.6.5.16.5 Over Speed Valve Testing (Re-Inspection) x A category 5 test shall be performed on the overspeed valve. 9/2/2022
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Evacuation procedures are missing from the MCP. 5/10/2023
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 Fire service testing must be documented monthly. 11/26/2024