Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Replace Phase II fire recall operation instructions.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be obtained and posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Fire service phase two instructions shall be legible.
MO Minimum : Elevators (S) - Fire Service (S)1 x x Phase 2 fire service shall be operational. Elevator not red tagged because this location is a busy hospital. This violation shall be repaired in 15 days of less, otherwise the elevator will be red tagged. 8/18/2021
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator.
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 8/18/2021
MO Minimum : Elevators (S) - Fire Service (S)1 x x Repair Phase II fire recall, car will not take call. Did not red tag because of hospital/location. Provide 45 days for correction. 7/7/2021