A17.1-2016 : Elevators
|
3.17 - Door and gate equipment
|
2.11.11.8
|
|
|
Hoistway doors are missing fire stop gibs.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Need to provide 19 ft candles of illumination in the machine space
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.17 - Door and gate equipment
|
2.11
|
|
|
Hoistway doors are missing fire stop gibs
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
8.6.11.1 Firefighters Emergency Operation: Monthly Testing
|
|
|
MCP Fire service testing must be properly documented monthly on log sheet.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
|
|
Need to provide 19 foot candles of illumination in the machine space.
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Battery lowering shall work. Battery lowering unit did not work on 4/9/2024 or 7/24/2024. (2nd Notice)
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.17 - Standby power operation
|
2.27.2
|
x
|
|
Battery lowering shall work. Repair or replace and re-test.
|
7/24/2024
|