A17.1-2016 : Elevators
|
1.4 - Sills and car floor
|
2.11.10.2
|
|
|
Illumination at Landing Sills: The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 fc. Note: Some lobbies are under construction, and not lighted.
|
3/15/2022
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.9 - Floor and emergency identification numbering
|
2.29.1
|
|
|
The identification number for each elevator shall be painted on, engraved, or securely attached adjacent to or on every elevator entrance at the designated level, and shall be a minimum of 3 inches in height.
|
7/3/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
|
|
Permanent electric lighting shall be provided in all machine rooms and machinery spaces. The illumination shall be not less than 19 foot-candles at the floor level. Note: The secondary space is not lighted.
|
7/3/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
|
|
Access doors to machine rooms and overhead machinery spaces shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. Note: The secondary access door doesn't meet these requirements.
|
7/3/2025
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
x
|
|
Current State operating certificate shall be displayed in the equipment room in a non-combustible fram. (previously cited re-inspection to enforce)
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.4 - Sills and car floor
|
2.11.11.1
|
x
|
|
The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10fc. (previously cited re-inspection to enforce)
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
2.3.2
|
x
|
|
The buffers, Governor tail sheave, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background. (cited previously re-inspection to enforce)
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1 Lighting
|
x
|
|
Permanent electric lighting shall be provided in all machine rooms and machinery spaces. The illumination shall be not less than 19 foot-candles at the floor level in the Primary Machine room (previously cited re-inspection to enforce)
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.1 - Access to machine space
|
2.7.3.4
|
x
|
|
Access doors to machine rooms and overhead machinery spaces shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. (previously cited re-inspection enforce)
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.28 - Counterweight and counterweight buffer
|
2.21
|
|
|
Bottom counterweight roller shall be replaced.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
3.8 - Top emergency exit
|
8.11.2.1.3(l)
|
|
|
Top emergency exit shall be properly secured.
|
|
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
: Pit shall be kept clean. Remove excess debris, Water noted in pit as well.
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The buffers, pit channels, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background.
|
3/15/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022)
|
3/15/2022
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door.
|
3/15/2022
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
3/15/2022
|