Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 3/15/2022
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 3/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.1 - Access to machine space 2.7.3.4 Access doors to machine rooms and overhead machinery spaces shall be self-closing and self-locking and shall be operable from the interior space without the use of a key. Note: The secondary access door doesn't meet these requirements.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers An ABC fire extinguisher with a current test tag shall be mounted in the machine room located convenient to the access door. 3/15/2022
A17.1-2016 : Elevators 1.4 - Sills and car floor 2.11.10.2 Illumination at Landing Sills: The building corridors shall be so lighted that the illumination at the landing sills, when an elevator is in service, shall be not less than 10 fc. Note: Some lobbies are under construction, and not lighted. 3/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.3 - Lighting and receptacles 2.7.5.1 Permanent electric lighting shall be provided in all machine rooms and machinery spaces. The illumination shall be not less than 19 foot-candles at the floor level. Note: The secondary space is not lighted.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.7 Signs and Data Plates The buffers, pit channels, and/or the compensating sheave assembly, which are visible from the pit access door, shall be marked with the car identification number with a minimum of 2 inches in height and of a contrasting color to its background. 3/15/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.9 - Floor and emergency identification numbering 2.29.1 The identification number for each elevator shall be painted on, engraved, or securely attached adjacent to or on every elevator entrance at the designated level, and shall be a minimum of 3 inches in height.