Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light & alarm bell not working. Re-inspection required 12/20/2022
MO Minimum : Elevators (S) - Fire Service (S)1 x x Doors do not open when recalled in Fire Fighters Emergency Service, runs between 1 and 2 without opening doors, even using door button. Red-tagged, Re-inspection required 2/13/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Inside of car call buttons are inoperable and shall be repaired to ensure safety for all elevator use. 9/18/2024
A17.1-2016 : Elevators 6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3) 8.6.11.1 Firefighters’ Emergency Operation x x Phase 1 recall inoperable and shall be repaired to meet the correct fire service requirements. 9/18/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in machine room is inadequate, repair existing light fixtures and add additional lighting in front of controller to provide at least 10 fc at floor 11/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Machine leaks oil onto floor, into hoistway, needs repaired 11/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Lighting in the machine room is inadequate, repair existing light fixtures and add additional lighting in front of controller to provide at least 10 fc at floor 11/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts Machine leaks oil onto floor, into hoistway, need to repair same 11/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 11/26/2025
conversion conversion n/a Machine room lights out, repair 2/26/2024
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine leaking oil in hoistway. 11/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lights need repair. 10 ft candle minimum 11/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Display updated current operating certificate in machine room. 11/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Emergency light lens needs to be replaced. 11/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) Machine room lights shall be 10 ft candles. 11/26/2025