Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 2.27.3 Yes Yes Ph1 Audible signal shall not be active when the car is at the recall level. 11/26/2025
A17.1-2016 : Elevators 2.29 - Car and counterweight safeties 2.17.3 Yes Yes Car safety slide shall be between 4"-22" 11/26/2025
conversion conversion n/a No No Clean oil and rags off car top 2/26/2024
conversion conversion n/a No No Machine room lights out toward the back - repair. 2/26/2024
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lights need repair. 10 ft candle minimum 11/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Clean oil and rags off cartop. 11/26/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone not working. 12/12/2019
MO Minimum : Elevators (H) - Machine Rooms (H)4 No No Clean oil off of floor and machine. 11/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current operating certificate in machine room. 11/26/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) Yes No Emergency phone shall work. 8/5/2021
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lights need repair. 10 ft candle minimum 11/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door needs to be self closing and locking 11/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Display current state operating certificate in the machine room 11/26/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. REINSPECT REQUIRED 3/29/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) Yes Yes Suspension ropes are undersized with rouge. RED TAGGED 3/29/2022
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Car does not recall on fire service phase 1. RED TAGGED 3/29/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No Machine room lights need to be 10 ft candles minimum 11/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door needs to be self locking & self closing 11/26/2025
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current state operating certificate shall be displayed in the elevator machine room 11/26/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Machine room door shall be self closing 1/23/2026
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of current Missouri Operating Certificate needs to be displayed in machine room 1/23/2026
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be cleaned 1/23/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light shall work 1/23/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Yes No Door restrictor is missing parts. Replace same 6/11/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.4 Maintenance records No No Maintenance control program needs to be updated 1/23/2026
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Emergency phone is not working 6/11/2025