Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone line is not working. Re-inspection required 1/25/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Bell and Phone not Functioning (Red Tag) x x Emergency phone is not working. Red-tagged, Re-inspection required 2/8/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Lighting in cab and on cartop is not working. Power is temporarily disconnected 1/21/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Lights in the pit shall work. Power temporarily disconnected 1/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Fire extinguisher in machine room is expired. Have serviced or replaced 1/21/2026
MO Minimum : Elevators (H) - Machine Rooms (H)4 Machine room doors shall be self locking, replace missing lock mechanism 1/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x x Emergencyy alarm & light do not work. Red-tagged, Re-inspection required 2/8/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Emergency phone is not working, appears to have no live phone line. Re-inspection required 2/8/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Repair holes in machine room ceiling and fire caulk around copper pipe and sprinkler pipe penetrations thru walls in machine room to preserve fire rating.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Elevator has sprinkler head in machine room. Install heat detector within 2 feet of head and shunt trip disconnect system to remove power from elevator equipment in event sprinkler head releases water. Re-inspection required