Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) Yes No Cat 5 testing still needs to be performed. Re-inspection required 5/26/2026
MO Minimum : Elevators (A) - Hoistways (A)16 Yes No At the top of the hoistway all conduit junction boxes are required to have the proper covers installed. 5/26/2026
MO Minimum : Elevators (A) - Hoistways (A)16 No No At the top of the hoistway all conduit junction boxes are required to have the proper covers installed. 5/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. 5/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required. 5/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No The elevator ADA telephone inside the elevator is not working properly. Two-way communication could not be established. Repair/replace this phone for proper operation and passenger safety. Reinspection required.
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) Yes No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 5/26/2026
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No The elevator pit light did not work on the day of inspection, repair for proper illumination of the pit floor. 5/21/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1f (Stop Switch in Pits) Yes No The elevator pit exceeds 66” and is required a second stop switch in the pit that conforms to A17.1 1995 edition. 5/26/2026
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1f (Stop Switch in Pits) No No The elevator pit exceeds 66” and is required a second stop switch in the pit that conforms to A17.1 1995 edition. 5/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate Yes No There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 5/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.5 Code Data Plate No No There is no code data plate found on the equipment to indicate the code and edition that the elevator was installed to, as used for all inspections. Provide a proper plate on the front of the controller or mainline disconnect. 5/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods Yes No The car traveling cable, underneath the car, has rubbed through the outer insulation in a couple of locations as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable. 5/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods No No The car traveling cable, underneath the car, has rubbed through the outer insulation in a couple of locations as the car reaches the lobby. Confirm that no internal wires have been affected and repair or replace traveling cable. 5/21/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Yes No The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2023 5/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2023 5/21/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 5/26/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required. 5/21/2026
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No This elevator has a backup emergency generator power that is used in case of a power outage. This system shall be scheduled to be tested and a reinspection is required. This requirement is due to the State of Missouri adopting the A17.1 2016 version of the elevator safety code. Reinspection required.
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars Yes No The elevator car top shall be cleaned of spare parts. 5/26/2026
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No The elevator car top shall be cleaned of spare parts. 5/21/2026