Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (A) - Hoistways (A)16 Low voltage coaxial cable has been installed in hoistway, only items relating to the operation of the elevator are allowed to be installed in the hoistway, remove coaxial cable
MO Minimum : Elevators (I) - Pits (I)1 The elevator pit is covered in water, the pit shall be kept clean & dry
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be on display in the elevator machine room.
MO Minimum : Elevators (A) - Hoistways (A)16 Low voltage coaxial cable has been installed in the elevator hoistway, only items related to the operation of the elevator are allowed to be installed in the elevator hoistway, need to remove coaxial cable from the hoistway.
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x When on Phase II, car opens with pressing the door opens, but does not immediately close, when the door open button is released, needs repaired. Re-inspection required
MO Minimum : Elevators (A) - Hoistways (A)13 The elevator hoistway shall be fully enclosed as follows: Enclosures shall be unperforated to a height of 6 ft above each floor or landing and above the treads of adjacent stairways. Unperforated enclosures shall be so supported and braced as to deflect not over 1" when subjected to a force of 100 lbs applied horizontally to any point, Open work enclosures may be used above the 6 ft level and shall reject a ball 2" in diameter. Machine room next to machine
conversion conversion n/a Only pipes wiring and duct used in connection with the elevator can be in hoist way 1/23/2019
conversion conversion conversion - reinspect x Phase II operation not working properly 1/28/2019
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)1(A) x Broken rope lays disconnected on number 3 cable. Re-rope car and redo safety test. 2/1/2019
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) x Repair alarm bell. 11/12/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Place current state operating certificate in elevator machine room. 1/15/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting Lighting in elevator cab shall be guarded to prevent breakage. 1/15/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)3 Provide means to lock cartop emergency exit. 1/15/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Emergency stop switch in cab is not fastened (broken). 1/15/2021
MO Minimum : Elevators (H) - Machine Rooms (H)8 Remove and reroute temporary low and high voltage wiring at machine space above hoistway. Shall comply with NFPA 70. 1/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Light ray door protection not installed on its own circuit. Reconnect light ray to door protection circuit. 1/7/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements Repair flexible conduit to car top lighting. 1/7/2022
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Elevator hoisting ropes are showing a high degree of wear and shall be replaced, replace ropes within 30 days of inspection 3/25/2022