A17.1-2016 : Elevators
|
6.3 - Firefighters' service (A17.1-1984 through A17.1a-1988 and A17.3)
|
8.6.11.1 Firefighters’ Emergency Operation
|
|
|
Rear doors should not open when returned to main landing, needs repaired.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.5.5.1 Examination and Maintenance
|
|
|
Need to repair Victaulic fitting in pump unit that is leaking
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the machine room
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Phone in elevator cab does not work.
|
11/12/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emregency phone fails to connect to front desk during activation.
|
5/13/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Need to install gutter under drain pipe to protect controller from water damage
|
6/10/2022
|