Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light did not function 4/3/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) x Emergency light not installed 4/3/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.13 - Windows, projections, recesses, and setbacks 2.11.10 Fascia not installed 2nd floor to 7th floor 6/17/2020
A17.1-2016 : Elevators 3.20 - Governor rope 8.11.2.1.3(z) x Governor rope is rouged, replace rope and test pull through