Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.4 - Sills and car floor 1001.2(a)(4) Fill gap in car flooring at the entrance (tripping hazard) 10/18/2022
A17.1-1996 : Elevators 1.4 - Sills and car floor 1001.2(a)(4) Replace missing floor strip on L1 & LD level at access to the car (tripping Hazard) 10/18/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair emergency phone in car 6/3/2021
A17.1-1996 : Elevators 2.3 - Lighting and receptacles 101.5a Lighting x Machine room lighting shall not be less than 200 lux/19fc at floor. 9/19/2023
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator, annually.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 8.6.11.1 Firefighters’ Emergency Operation Documentation Perform monthly fire service and document on log in machine room 10/18/2022
A17.1-2016 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Car Emergency System (Re-Inspection) x Emergency lighting shall work.