Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 5.11 - Plunger and Cylinder 8.6.5.5 Must replace Jack Packing Gland to limit oil loss. 8.6.5.5.1 9/18/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits Pit must be kept Free of Water and Oil. 8.6.4.7.4 ( Currently 1' standing water in pit) 9/18/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3.2 Phase I Operation Recall by Initiating Device x x FAID must be tested, machine room smoke failed to initiate recall. 10/3/2024
A17.1-2016 : Elevators 2.6 - Ventilation 2.7.9.2 x Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means. 10/3/2024
A17.1-2016 : Elevators 2.11 - Disconnecting Means and Control 2.26.4.5 x Disconnects shall be labeled with location of feeder breakers. 10/3/2024