A17.1-2016 : Elevators
|
5.11 - Plunger and Cylinder
|
8.6.5.5
|
|
|
Must replace Jack Packing Gland to limit oil loss. 8.6.5.5.1
|
9/18/2025
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Pit must be kept Free of Water and Oil. 8.6.4.7.4 ( Currently 1' standing water in pit)
|
9/18/2025
|
A17.1-2016 : Elevators
|
2.6 - Ventilation
|
2.7.9.2
|
x
|
|
Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means.
|
10/3/2024
|
A17.1-2016 : Elevators
|
6.4 - Firefighters' service (A17.1b-1989 and later editions)
|
2.27.3.2 Phase I Operation Recall by Initiating Device
|
x
|
x
|
FAID must be tested, machine room smoke failed to initiate recall.
|
10/3/2024
|
A17.1-2016 : Elevators
|
2.11 - Disconnecting Means and Control
|
2.26.4.5
|
x
|
|
Disconnects shall be labeled with location of feeder breakers.
|
10/3/2024
|