Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 2.11 - Disconnecting Means and Control | 2.26.4.5 | x | Disconnects shall be labeled with location of feeder breakers. | 10/3/2024 | |
A17.1-2016 : Elevators | 6.4 - Firefighters' service (A17.1b-1989 and later editions) | 2.27.3.2 Phase I Operation Recall by Initiating Device | x | x | FAID must be tested, machine room smoke failed to initiate recall. | 10/3/2024 |
A17.1-2016 : Elevators | 2.6 - Ventilation | 2.7.9.2 | x | Provide machine room ventilation to meet OEM temperature/humidity requirements. Can be natural or mechanical means. | 10/3/2024 |