Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No no current cirt. displayed 6/24/2021
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes Yes phase one fire serv.failure door closes when on fire serv buy its self 2/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No emg. bell not working 2/10/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1- 8.6.4.15 Car Emergency Systems (Emergency Light) (Re-Inspection) Yes No only one emergency light bulb came on 5/20/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No alarm bell is not loud enough to be heard over the ambient noise in the building 5/20/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days) Yes No no dial tone on the emergency phone 5/20/2022
MO Minimum : Elevators (H) - Machine Rooms (H)5 (Machine Room Lighting) No No replace burnt out light bulbs over the controller in the machine room 3/29/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No the fire service phase 1 keyswitch is mounted upside down to the markings on the faceplate 3/29/2023
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No the fire hat jewel visual indicator on the car operating panel did not light on fire service recall 5/20/2022
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No the fire service phase 1 keyswitch, the key shall be removable in the on position 4/14/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No on fire service phase 2 when traveling to the bottom landing the elevator stops at the middle landing about 2 feet below the sill level and opens the car doors 4/14/2023
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No on fire service phase 2, the doors close automatically after momentarily pressing the door close button, the instructions say door close is constant pressure, either the instructions are wrong or the operation is wrong 4/14/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Fire extinguisher inspection tag is expired, have fire extinguisher inspected annually 4/2/2025
MO Minimum : Elevators (I) - Pits (I)6 (Pit Lighting) No No Pit light did not work, repair pit light, fixture has been water damaged 4/2/2025