Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
A17.1-2016 : Elevators | 2.36 - Hydraulic Cylinders | 8.6.5.5.2 Collection of Oil Leakage | x | Oil Recovery unit the pit does not allow for documenting oil loss as required by the state of Missouri, and A17.1 8.6.5.5.2. Oil recovery units may only be used temporarily if the packing gland is leaking, until the packing gland of the jack can be replaced. After this point , oil recovery unit must be removerd and an oil collection container must be used. | 11/24/2021 | |
A17.1-1996 : Elevators | 1.15 - sign and operating device symbols | 1001.2(a)(15) | Provide "in case of fire use stairs" signs at all landings ( a17.1 1996, appendix H) | 1/10/2020 |