| MO Minimum : Elevators | (A) - Hoistways | (A)13 |  |  | Must replace Missing/damaged Sheetrock at top of hoistway. | 4/9/2025 | 
                
                    | MO Minimum : Elevators | (B) - Car Enclosure: Passenger | (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) | x |  | Provide operational telephone in elevator cab | 2/2/2023 | 
                
                    | A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a |  |  | Install a fire damper in the HVAC duct added at the top of the machine room wall. this is a rated fire assembly | 2/2/2023 | 
                
                    | A17.1-1996 : Elevators | 2.4 - Machine space | 101.1a |  |  | Patch the hole cut into the wall to access and repair the plumbing, near the bottom of the wall. This is a fire rated assembly | 2/2/2023 | 
                
                    | A17.1-1996 : Elevators | 3.10 - Hoistway construction | 100 |  |  | Stop the roof leaking and patch the ceiling back to a 1 hour rated assembly. This is a fire rated assembly. | 2/2/2023 | 
                
                    | A17.1-1996 : Elevators | 3.10 - Hoistway construction | 1001.2(c)(16) |  |  | Patch the hole in the drywall in the hoistway inside to the left of the door between the 1st. and 2nd. floors. | 1/24/2019 |