Code | Item | Section | Reinspection | Red Tag | Reason For Violation | Fixed Date |
---|---|---|---|---|---|---|
MO Minimum : Elevators | (S) - Fire Service | 211.3a(8) Visual and audible signal | The fireman’s emergency service phase I visual signal (inside the elevator car) is worn off due to excessive cleaning. Replace visual signal for indication to passengers and emergency personnel. | |||
A17.1-2016 : Elevators | 1.17 - Standby power operation | 8.6.4.19.7 (Re-Inspection) | x | Elevators connected to an emergency generator shall be tested for operation on emergency power. Re-inspection required | 4/16/2024 |