A17.1-1996 : Elevators
|
1.5 - Car lighting and receptacles
|
204.7
|
|
|
Emergency light not working on battery back-up. 1.5.1
|
5/26/2020
|
A17.1-1996 : Elevators
|
2.40 - Maintenance Records
|
210.1d Inspection Operation.
|
|
|
Maintenance records are required to be in the machine room.
|
5/26/2020
|
A17.1-1996 : Elevators
|
2.41 - Maintenance Records
|
8.6.1.4
|
|
|
A copy of the MCP shall be kept in the machine room for each elevator
|
1/5/2023
|
A17.1-1996 : Elevators
|
1.6 - Car emergency signal
|
211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency phone not working. Re-inspection required
|
2/28/2023
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
6/7/2023
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
Provide current tested fire extinguisher in the elevator machine room.
|
6/7/2023
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
Relief pressure =160, tried 3 different gauges to verify. Determine cause of low pressure. 14 DAYS to reinspect.
|
11/9/2023
|