Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light not working on battery back-up. 1.5.1 5/26/2020
A17.1-1996 : Elevators 2.40 - Maintenance Records 210.1d Inspection Operation. Maintenance records are required to be in the machine room. 5/26/2020
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A copy of the MCP shall be kept in the machine room for each elevator 1/5/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 6/7/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current tested fire extinguisher in the elevator machine room. 6/7/2023
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Fire service shall be tested once the car is considered safe
A17.1-2016 : Elevators 2.32 - Control Valve 8.6.5.5.1 Examination and Maintenance x x There is a major leak in the system that is causing the car to leak down an inch per minute, need to determine where the leak is and correct the problem. This unit is being Red-tagged, Re-inspection required for static test once the problem has been resolved. 2/25/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Relief pressure =160, tried 3 different gauges to verify. Determine cause of low pressure. 14 DAYS to reinspect. 11/9/2023
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Re-inspection required 2/28/2023