Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Relief pressure =160, tried 3 different gauges to verify. Determine cause of low pressure. 14 DAYS to reinspect. 11/9/2023
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7 Emergency light not working on battery back-up. 1.5.1 5/26/2020
A17.1-1996 : Elevators 2.40 - Maintenance Records 210.1d Inspection Operation. Maintenance records are required to be in the machine room. 5/26/2020
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Emergency phone not working. Re-inspection required 2/28/2023
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current State Elevator Certificate. 6/7/2023
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A copy of the MCP shall be kept in the machine room for each elevator 1/5/2023
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers Provide current tested fire extinguisher in the elevator machine room. 6/7/2023