Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.17 - Drive machine brake 1002.3d x Complete brake test. 11/21/2019
A17.1-1996 : Elevators 5.9 - Buffers and emergency terminal speed limiting devices 1308.2 x Complete buffer test. 11/21/2019
A17.1-1996 : Elevators 2.42 - Earthquake Inspection and Tests (Seismic Risk Zone 2 or Greater) 8.4.10.1.2 - Protection not functioning x Elevator shall move away from counterweight and park with doors open when switch is activated. Re-inspection required 7/18/2023
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are rouged and are at a minimum allowable diameter. Replace ropes within 60 days. Re-inspection required 8/21/2024
MO Minimum : Elevators (L) - Wire Ropes-Hoisting, Governor and Tiller (L)12 (Re- Inspection) x Suspension ropes are rouged and at a minimum allowable diameter. Replace ropes within 60 days. Re-inspection required 12/3/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Test incomplete, need to perform the following test to complete inspection: No load, Full speed counterweight buffer testing. Re-inspection required 8/21/2024