ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing
|
|
|
This elevator is equipped with an over speed valve that in not sealed. A category 5 test shall be performed on the over speed valve in 2021 or 2022. The valve shall be sealed and tagged after the category 5 test.
|
11/23/2021
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.13 - Emergency exit
|
2.14.1.5
|
|
|
A new latch on the car top emergency exit shall be provided.
|
8/15/2025
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
8.6.5.16.5 Over Speed Valve Testing (Re-Inspect)
|
x
|
|
This elevator is equipped with an unsealed overspeed valve. A category 5 test shall be performed and witnessed in 2022. The valve shall be tagged and sealed after the category 5 test.
|
11/1/2022
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.7 Signs and Data Plates
|
|
|
The tactile elevator signage shall correctly identify the correct egress floor for Fire Service. The main landing shall be labeled as the egress floor and the lower landing shall be only labeled as the lower landing only and not the egress floor.
|
|