Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 2.27.2 Yes No Emergency standby generator power operation needs to be tested with full capacity. Re-inspection required 9/8/2026
A17.1-2016 : Elevators 6.5 -Acceptance Checklist for Firefighters' Service (ASME A17.1-2000 and CSA B44-00): Automatic Elevators 3.27 Emergency Operation and Signaling Devices Yes No Need to correct fire service issues: 10 add heat detectors in top of hoistway (one for each sprinkler head) and connect the shunt trip system to remove power to elevator if sprinklers go off 2) car gate does not close allowing car to return to main floor on recall when Phase I is turned off. 3) Door/gate light curtains are not overridden when on Fire Service 4) Phase I fire service panel in car needs to have rear door open and close buttons 5) smoke detectors on first floor bring elevator at that floor and do not send elevator to auxiliary floor. Re-inspection required 9/8/2026
MO Minimum : Elevators (I) - Pits (I)1 No No There is a cast iron water pipe that runs vertically in the hoistway that is leaking into the elevator pit 8/2/2023