Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) Yes No Provide testing on emergency power. 8/9/2024
A17.1-2016 : Elevators 4.12 - Standby power selection switch 8.6.4.19.7 (Re-Inspection) Yes No Provide testing. 8/9/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) No No Emergency exit shall be operable, remove temporary weights from top of hatch. 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers No No Pit sump pump hole is not covered. 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) No No Counterweights are compressing buffer in pit when car is at top landing. Shorten ropes to provide minimum runby of 6" 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No No maintenance records on site. 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.8 - Top emergency exit 8.11.2.1.3(l) No No Emergency hatch shall be operable. Remove temporary weights from top of hatch. 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No Written maintenance control program shall be provided on site. 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 2.2.2.6 Sump Pump Covers No No Sump pump hole shall be covered. 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.28 - Counterweight and counterweight buffer 8.11.2.1.3(m) No No Counterweights are compressing buffer in pit when car is at the top landing. Hoist ropes need to be shortened to get minimum runby of 6". 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 No No No maintenance control program in the machine room 4/14/2022
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.6 - Car emergency signal 8.11.2.1.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Emergency phone does not work. 3/2/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Clean oil off of pit floor. 10/14/2025
MO Minimum : Elevators (F) - Electrical Switches (F)6 Yes No Re-install buffer switches on car and counterweights. 10/14/2025
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (1) Minimum Standard Yes No Test incomplete. Car top still needs to be inspected 10/12/2021