Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. The diagrams in the machine room are incomplete.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/19/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams A legible copy of the up to date wiring diagrams shall be kept on site. 6/19/2020
A17.1-2016 : Elevators 5.4 - Normal terminal stopping devices 3.25.1 The bottom normal terminal stopping device (down directional limit) shall be adjusted to stop the car before it rests on the car buffer. 6/19/2020
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Written evacuation procedures for elevators by authorized persons and emergency personnel shall be available on-site. 5/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. (This item is for notification purposes for future violation in 2022) 5/1/2021
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 6/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 2.41 - Maintenance Records 8.6.1.4 Up-to-date wiring diagrams shall be provided and permanently kept in the machine room. The diagrams in the machine room are incomplete. 6/21/2023
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 3.5 - Normal terminal stopping device 2.25.2 x The down directional limit shall stop the car before landing on the buffers. The elevator lands on the buffers several inches before actuating the down directional limit. 1/10/2024
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators 1.5 - Car lighting and receptacles 8.6.4.15 Emergency Lighting x Emergency lighting shall work. 8/21/2024