MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
Yes
|
Yes
|
"HOLD" doesn't work on Phase II fire service
|
7/17/2020
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.13 - Door systems
|
Yes
|
No
|
Replace broken pickup rollers on the second landing hoistway door (Reinspect)
|
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
Yes
|
No
|
The personnel answering the emergency phone could not communicate with the person in the elevator cab due to distortion on the phone line.
|
6/19/2025
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.2.1 Repair Parts
|
Yes
|
No
|
The Phase II key switch is falling out of it's mount. Any pressure on the key switch causes it to fall into the COP.
|
6/19/2025
|