A17.1-2016 : Elevators
|
1.6 - Car emergency signal
|
2.27.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days)
|
x
|
|
Existing phone works, but has bad microphone. Repair/replace as needed.
|
|
A17.1-2016 : Elevators
|
5.1 - Pit access, lighting, stop switch, and condition
|
8.6.4.7 Cleaning of Pits
|
|
|
Remove fluid from the pit.(water)
|
|
A17.1-2016 : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post current State Elevator Certificate.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
Emergency light and alarm bell not working.
|
5/26/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.4.15 Car Emg Sys (Phone or alarm not functioning Mandatory Re-Inspection due in 14 days)
|
x
|
|
Emergency lights and bell do not work.
|
3/9/2021
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Provide Phase I operating procedures need to be posted near key switch in lobby.
|
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Phase II operation failed. Did not red tag - Repair required by 6/16/20 or will be taken out of service.
|
3/9/2021
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
Remove all non-elevator equipment from machine room.
|
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)8 Car Lighting
|
|
|
Provide guard on car bulbs.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - 8.6.1.6.3 Controllers ,Wiring and Wiring Diagrams
|
|
|
Label all relays on controller.
|
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.4 Maintenance records
|
|
|
Provide missing oil loss log.
|
|
MO Minimum : Elevators
|
(I) - Pits
|
(I)1
|
|
|
Remove water from pit.
|
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A copy of the current state operating certificate shall be displayed in the elevator machine room
|
11/1/2023
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Phase II does not keep door in open position. Repair shall be made and re-inspected within 30 days
|
11/16/2022
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
|
No audible sound when elevator is on Phase I. Re-inspection required
|
11/16/2022
|