Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 5/28/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Alarm bell is not working. Re-inspection required 1/30/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Car handrails are loose, need to be tighten as needed 5/28/2025
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal Yes No Car shall have a visual light that works on Phase I. Re-inspection required 9/19/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.4.9 Cleaning of Top of Cars No No Clean car top 5/28/2025
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) Yes No Light ray is not overridden in Phase I. Repair & re-inspect in 15 days 9/19/2022
MO Minimum : Elevators (H) - Machine Rooms (H)2 Yes No Machine room ceiling is leaking water onto emergency lowering equipment. Re-inspection required
MO Minimum : Elevators (S) - Fire Service (S)1 Yes No On Phase 1 and 2 fire service, car door re-opening device (light ray) is not overridden. Light ray shall be overridden on fire service. 11/4/2019
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase I (in car) visual indicator does not work. 3/9/2021
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage No No Phase I operating procedures need to be posted near key switch in lobby. 5/28/2025
MO Minimum : Elevators (S) - Fire Service (S)1 Yes Yes Phase II operation failed. Repair and retest by 6/16/20 or unit will be red tagged and removed from service. 3/9/2021
MO Minimum : Elevators (I) - Pits (I)1 No No Pit needs to be clean and dry
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 5/28/2025
A17.1-2016 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No Post current State Elevator Certificate. 5/28/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)8 Car Lighting No No Provide cover for bulbs in car. 5/28/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 3.27 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No Provide existing alarm bell to work (also check on 110v. disconnect off). 9/20/2024
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) Yes No Provide existing alarm bell to work. 11/21/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts No No Provide existing top of car light to work 5/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers No No Provide updated fire extinguisher in machine room. 5/28/2025
MO Minimum : Elevators (H) - Machine Rooms (H)2 No No Remove all non-elevator related equipment from elevator machine room. 5/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 Maintenance, Repair and Replacements No No Repair 3rd floor button, relay is mechanically blocked 5/28/2025
MO Minimum : Elevators (O) - Existing Hydraulic Elevators (O)1 No No Return line to tank is constantly dripping. Replace packing. 5/28/2025
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)1 No No Tighten car hand rails as needed. 5/28/2025
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No Top of car light not working, make so. 5/28/2025