Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators 2.6 - Ventilation 1001.2(b)(6) Have the AC unit repaired as it don't cool. 2/23/2024
A17.1-1996 : Elevators 3.17 - Door and gate equipment 1001.2(c)(23) Have the door sill and sill support replaced as it is rusted and causing the sill to be raised up and stopping the door from closing . 2/23/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Have the fire extinguisher re-certified 2/23/2024
A17.1-1996 : Elevators 2.7 - Fire Extinguisher 1001.2(b)(7) Have the fire extinguisher re-certified as it is expired. 3/10/2020
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 2/22/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 2/21/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair or Replace the non working emergency phone. 3/21/2019
conversion conversion n/a Replace the broken fire service key switch. It will not turn. 7/27/2018
conversion conversion n/a Replace the emergency light battery as it is dead 7/27/2018
A17.1-1996 : Elevators 1.6 - Car emergency signal 306.11 (Hydro) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Replace the emergency phone as it is dead has no signal 3/15/2023
A17.1-1996 : Elevators 1.4 - Sills and car floor 1001.2(a)(4) Replace the hoistway sill and sill support angle as it is oxidized to a point it is causing the sill to buckle up and and bind up the hoistway door so it will not open and close properly 3/10/2020