Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Provide a usable phone line foro emergency phone. 8/12/2019
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Repair or replace the emergency phone as it does not dial out., 7/30/2021
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as there is no dial tone 10/12/2022
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x Repair the emergency phone as the phone will not dial out 8/7/2023
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)11 Phone or alarm not functioning ( Mandatory Re-Inspection due in 14 days) x emergency phone still not working 8/11/2023
MO Minimum : Elevators (H) - Machine Rooms (H)2 Replace the machine room door lock as it will not allow entrance, no key. 7/30/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Repair or replace the door closer on the machine room door as it is to be self closing and self latching. 7/30/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Replace the missing machine room door closer as it is to be self closing. self latching 7/30/2021
MO Minimum : Elevators (H) - Machine Rooms (H)2 Provide a always locked outside and never locked inside door lock on the machine room door 7/30/2021
MO Minimum : Elevators (H) - Machine Rooms (H)8 Elemonate the use of the extensioin cord in the machine roo to the AC unit. 7/30/2021
MO Minimum : Elevators (I) - Pits (I)1 Have the sump pump srviced as it is not working and remove the standing water from the pit. 7/30/2021
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.15 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x Repair or replace the emergency phone as it has no dial tone the incoming line is dead 6/6/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Obtain and display a current state operating certificate in the machine room 7/30/2021