Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post current state operating certificate inside machine room 11/12/2025
A17.1-1996 : Elevators 2.9 - Guarding of exposed auxiliary equipment 104.1 Install guarding over drive sheave and hoist ropes where they extend past the base of the machine 11/12/2025
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictors not working.
A17.1-1996 : Elevators 2.18 - Traction drive machines 208 Traction machine very noisy during operation. More testing required to determine source of noise, then repair as necessary.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.6.4.19.7 (Re-Inspection) x Verify emergency power operation 11/13/2024