Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
conversion conversion n/a Door closing force shall be less than 30 6/3/2019
conversion conversion n/a Fill All Voids in hoisway in pit area - 1 near top of hoistway 6/3/2019
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/15/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The machine room fire extinguisher shall have a current test tag. 5/15/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 The door closing force shall be adjusted so it does not exceed 30 pounds. 5/15/2020
MO Minimum : Elevators (A) - Hoistways (A)13 The holes in the pit wall, and near the top of the hoistway shall be sealed with approved solid materials. 5/15/2020
MO Minimum : Elevators (B) - Car Enclosure: Passenger (B)7 Door closing force shall be adjusted, not to exceed 30 pds. 7/25/2020
MO Minimum : Elevators (A) - Hoistways (A)13 Seal holes in pit wall and near top of hoistway. 7/25/2020
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Post operating certificate in equipment room. 4/6/2021
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6.5 Fire Extinguishers The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2022. 5/15/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. 5/15/2024
MO Minimum : Elevators (S) - Fire Service 211.7 Firefighters Operations/Signage Provide signage to meet the code date of the Fire recall system (No Hold for this vintage 5/15/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.3.1 Replacement Parts Provide 2 separate car light sources 5/15/2024
MO Minimum : Elevators (H) - Machine Rooms (H)2 The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key. 5/15/2024
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Reinspection is required. 5/1/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair inoperable audible and visual Phase I indicators 4/9/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Repair Phase II key switch. Hold position not functioning 4/9/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Stop switch not overridden in Phase 1 4/9/2024
MO Minimum : Elevators (S) - Fire Service 8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection) x Car not returning to Phase I when Phase II key is switched to off 4/9/2024
MO Minimum : Elevators (S) - Fire Service 211.3a(8) Visual and audible signal x x Repair inoperable audible and visual Phase I indicators. Initially sited 5/26/23. 5/1/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x x Repair Phase II key switch. Hold position not functioning. Initially sited 5/26/23. 5/1/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x x Stop switch not overridden in Phase 1. Initially sited 5/26/23. 5/1/2024
MO Minimum : Elevators (S) - Fire Service (S)1 x x Car not returning to Phase I when Phase II key is switched to off. Initially sited 5/26/23. 5/1/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The emergency lighting shall be operational. 8/14/2020
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting) x The alarm bell shall be operational on auxiliary power. 8/14/2020
MO Minimum : Elevators (S) - Fire Service (S)1 x Remove the Phase 1 fire service key switch at the basement level. 7/17/2019
conversion conversion conversion - reinspect x On Phase II door does not close when door open button is released 5/8/2019