conversion
|
conversion
|
n/a
|
|
|
Door closing force shall be less than 30
|
6/3/2019
|
conversion
|
conversion
|
n/a
|
|
|
Fill All Voids in hoisway in pit area - 1 near top of hoistway
|
6/3/2019
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it.
|
5/15/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The machine room fire extinguisher shall have a current test tag.
|
5/15/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
The door closing force shall be adjusted so it does not exceed 30 pounds.
|
5/15/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
The holes in the pit wall, and near the top of the hoistway shall be sealed with approved solid materials.
|
5/15/2020
|
MO Minimum : Elevators
|
(B) - Car Enclosure: Passenger
|
(B)7
|
|
|
Door closing force shall be adjusted, not to exceed 30 pds.
|
7/25/2020
|
MO Minimum : Elevators
|
(A) - Hoistways
|
(A)13
|
|
|
Seal holes in pit wall and near top of hoistway.
|
7/25/2020
|
MO Minimum : Elevators
|
CSR 40-5.100 State Operating Certificate
|
5.100(2) Display of Operating Certificate
|
|
|
Post operating certificate in equipment room.
|
4/6/2021
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.1.6.5 Fire Extinguishers
|
|
|
The fire extinguisher in the machine room shall be serviced, the last annual service tag indicates it was serviced in 2022.
|
5/15/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
|
5/15/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.7 Firefighters Operations/Signage
|
|
|
Provide signage to meet the code date of the Fire recall system (No Hold for this vintage
|
5/15/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
8.6.3.1 Replacement Parts
|
|
|
Provide 2 separate car light sources
|
5/15/2024
|
MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
The elevator machine room door shall be self-closing/self-locking and shall be operable from the interior space without the use of a key.
|
5/15/2024
|
MO Minimum : Elevators
|
11 CSR 40-5.090 Inspection and Testing
|
(3) Testing Procedures (Re-Inspect)
|
x
|
|
The testing has not been completed on the elevator at this time, the elevator was placed out of service. Only a machine room inspection was performed, a full inspection shall be performed before the annual is completed. Reinspection is required.
|
5/1/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair inoperable audible and visual Phase I indicators
|
4/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Repair Phase II key switch. Hold position not functioning
|
4/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Stop switch not overridden in Phase 1
|
4/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
8.11.2.2.6 Firefighters’ Emergency Operation (Re-Inspection)
|
x
|
|
Car not returning to Phase I when Phase II key is switched to off
|
4/9/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
211.3a(8) Visual and audible signal
|
x
|
x
|
Repair inoperable audible and visual Phase I indicators. Initially sited 5/26/23.
|
5/1/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Repair Phase II key switch. Hold position not functioning. Initially sited 5/26/23.
|
5/1/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Stop switch not overridden in Phase 1. Initially sited 5/26/23.
|
5/1/2024
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
x
|
Car not returning to Phase I when Phase II key is switched to off. Initially sited 5/26/23.
|
5/1/2024
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The emergency lighting shall be operational.
|
8/14/2020
|
MO Minimum : Elevators
|
(G) - Maintenance, Repair and Replacements
|
(G)1 - Car Emergency Systems - 8.6.4.15 (bell, phone & Emergency lighting)
|
x
|
|
The alarm bell shall be operational on auxiliary power.
|
8/14/2020
|
MO Minimum : Elevators
|
(S) - Fire Service
|
(S)1
|
x
|
|
Remove the Phase 1 fire service key switch at the basement level.
|
7/17/2019
|
conversion
|
conversion
|
conversion - reinspect
|
x
|
|
On Phase II door does not close when door open button is released
|
5/8/2019
|