Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators 11 CSR 40-5.090 Inspection and Testing (3) Testing Procedures (Re-Inspect) x Inspection of the hoistway and fire service need to be tested to complete the annual inspection. 2/23/2022
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements (G)1 - 8.6.4.13 - Door systems Pick up roller on floor 1 door needs adjusting. 7/10/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 1001.2(a)(17) x Elevators that are equipped to operate on emergency power shall be tested with no load in the car while operating on the emergency generator. 2/23/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The phone is hard to hear due to static. Take corrective action as needed. 2/23/2022
A17.1-1996 : Elevators 1.6 - Car emergency signal 1001.2(a)(6) (Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The phone is hard to hear due to static. Take corrective action as needed. 1/24/2023
A17.1-1996 : Elevators 2.11 - Disconnecting Means and Control 1001.2(b)(11) Label the disconnects with the location, source, and breaker numbers of the panel from which it is fed. 7/10/2024
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 1001.2(c)(18) The basement level interlock conduit shall be repaired. 7/10/2024
A17.1-1996 : Elevators 3.23 - Suspension rope 1001.2(c)(29) x There is a large amount of "Rope Dust" on the floor by the machine. Hoist Ropes appear dry and showing “rouge”. Ropes shall be cleaned and lubricated per OEM
A17.1-1996 : Elevators 2.4 - Machine space 101.2 Machine room lighting needs to be repaired, 1 or more bulbs not working.
A17.1-1996 : Elevators 2.1 - Access to machine space 101.3d Machine room door shall be self-closing and self-locking . There is no handle/lock on MR door.
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 The basement level interlock conduit shall be repaired or replaced. 7/10/2024
A17.1-1996 : Elevators 3.12 - Pipes, wiring, and ducts 102 The basement level interlock raceway shall be repaired or replaced. 7/10/2024
A17.1-1996 : Elevators 2.16 -Overhead Beam and Fastenings 105.3 Top of hoistway beam clamp has loose jamb nut (about to fall off bolt).
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 Pit shall be kept clean. Remove excess debris.
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Clean the pit. 7/10/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 The pit shall be kept clean. Clean the pit. 7/10/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1 There is water in the pit. The pit shall be kept clean and dry. Correct source of water leak. 7/10/2024
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits Clean the pit. 10/8/2019
A17.1-1996 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 106.1e Illumination of Pits The pit shall be kept clean. Clean the pit. 7/10/2024
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 110.11f(2) - Hoistway doors have loose guides on 7th floor. Repair/replace as needed.
A17.1-1996 : Elevators 3.17 - Door and gate equipment 110 110.11f(3) - Hoistway door gib fire tabs shall be engaged into the guideway(sill) : 8th floor.
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x Car door restrictor is missing. 7/15/2024
A17.1-1996 : Elevators 1.18 - Restricted opening of car or hoistway doors 111.5 Restricted Opening of Hall/Car Doors x The car door restrictor shall be operational. 2/22/2022
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2b (Clean Machine Room) 1206.2c - Clean the car top. 10/8/2019
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) Cartop shall be kept free of excess debris/dirt/lint.
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car top shall be cleaned. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car top shall be kept clean. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car-top shall be kept clean. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 2.5 - Housekeeping 1206.2c (Clean Car Tops) The car-top shall be kept clean. Clean the car top. 7/10/2024
A17.1-1996 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 1206.7 A record of findings for firefighters' service operation, tested monthly as required by 8.6.11.1 with identification of the person(s) that performed the operation, and the date shall be available on-site. 7/10/2024
A17.1-1996 : Elevators 1.5 - Car lighting and receptacles 204.7a (3)(a) Standby Illumination in the car. (Re-Inspection) x The in car emergency light shall be operational. Repair or replace as needed. 7/15/2024
A17.1-1996 : Elevators 1.6 - Car emergency signal 211.1 Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The emergency bell does not work. 7/15/2024
A17.1-1996 : Elevators 1.17 - Standby power operation 211.2 x The standby/emergency power indicator light at the egress floor shall illuminate when on emergency power operation. 3/6/2024
A17.1-1996 : Elevators 3.22 - Wire rope fastening and hitch plate 212 .9e(4) - Hoist Rope Tail retaining clips shall be properly spaced. Counterweight side.
A17.1-1996 : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 7/10/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and all the on-site documentation required by A17.1 2016 - 8.6.1.2.2 and 8.6.1.4 shall be provided in the machine room. Evacuation procedures are missing. 7/10/2024
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 A code compliant MCP and related on-site documentation shall be provided in the machine room. MCP hasn't been updated since 2022.
A17.1-1996 : Elevators 2.41 - Maintenance Records 8.6.1.4 Provide a code compliant MCP including onsite documents. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The emergency power indicator light shall activate when unit is operating on emergency power. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.1.6 General Maintenance Methods The pickup rollers at B & 1 shall be adjusted for proper operation. 7/10/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts x Car top handrail is bent. 7/15/2024
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The pit shall be kept clean and dry. 7/22/2020
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.6.4.7 Cleaning of Pits The sump pump in the pit shall be operational. 7/22/2020