Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A copy of the current state operating certificate shall be displayed in the machine room 5/20/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts No No The muffler leaks oil, repair. 5/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate No No A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate Yes No A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it 1/5/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications Yes No A visual indication on the same panel as the "PHONE" push button shall be provided to acknowledge that two-way communications link has been established. 1/5/2025
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) Yes No The two-way communication means within the car shall include a means to verify operablility of the line meeting the requirements of 2.27.1.1.6. If means other than a telephone line are used for two-way communications, similar verification of this equivlent means shall be performed. 1/5/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.7.2.15.2 Yes No The illuminated signal for emergency power shall operate as required. 1/5/2025
A17.1-2016 : Elevators 1.17 - Standby power operation 8.7.2.16.4 Yes No The car shall run correctly on emergency power. The car ran up to verify the ability to light the load, but would not respond after first run. 1/5/2025
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) Yes No The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone. 1/5/2025
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space Yes No Pieces of the drop ceiling are missing in the machine room and shall be installed/replaced. 1/5/2025
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 Yes Yes The new elevator controller is to be connected to the building security system. Once this is complete, a re-inspection shall be performed to verify it will be rendered inoperative when on fire service operation. 1/5/2025
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) Yes No The correct schematics shall be in the machine room 1/5/2025
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) Yes No The lighting in the pit shall provide an illumination of no less than 11 1X(10ft) at the pit floor. 1/5/2025
A17.1-2016 : Elevators 3.17 - Door and gate equipment 2.13 Yes No The door operator kinetic energy tag shall be filled out to indicate the minimum door closing times. 1/5/2025
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 Yes No A duplex GFCI receptacle shall be provided in the machine room. 1/5/2025
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 Yes No A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of section 8.7. 1/5/2025