Code Item Section Reinspection Red Tag Reason For Violation Fixed Date
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A copy of the current state operating certificate shall be displayed in the machine room 5/20/2024
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate A current MO State operating certificate shall be posted in the elevator equipment room, in a noncombustible frame with a clear protective vision plate over it. 5/20/2024
MO Minimum : Elevators (G) - Maintenance, Repair and Replacements 8.6.2.1 Repair Parts The muffler leaks oil, repair. 5/20/2024
A17.1-2016 : Elevators 3.17 - Door and gate equipment 2.13 x The door operator kinetic energy tag shall be filled out to indicate the minimum door closing times.
A17.1-2016 : Elevators 6.4 - Firefighters' service (A17.1b-1989 and later editions) 2.27.3 x x The new elevator controller is to be connected to the building security system. Once this is complete, a re-inspection shall be performed to verify it will be rendered inoperative when on fire service operation.
A17.1-2016 : Elevators 2.3 - Lighting and receptacles 2.8.2 x A duplex GFCI receptacle shall be provided in the machine room.
MO Minimum : Elevators CSR 40-5.100 State Operating Certificate 5.100(2) Display of Operating Certificate x A current MO State operating certificate shall be posted in the elevator equipment room, in a non-combustible frame with a clear protective vision plate over it
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.10.2.2.1(f) (Insp code) Phone or alarm not functioning (Mandatory Re-Inspection due in 14 days) x The two-way communication means within the car shall include a means to verify operablility of the line meeting the requirements of 2.27.1.1.6. If means other than a telephone line are used for two-way communications, similar verification of this equivlent means shall be performed.
A17.1-2016 : Elevators 5.1 - Pit access, lighting, stop switch, and condition 8.10.2.2.5(a) x The lighting in the pit shall provide an illumination of no less than 11 1X(10ft) at the pit floor.
A17.1-2016 : Elevators 2.40 - Maintenance Records 8.6.1.2.2(a) On-Site Documentation (Up-to-Date Wiring Diagrams) x The correct schematics shall be in the machine room
A17.1-2016 : Elevators 1.18 - Restricted opening of car or hoistway doors 8.6.4.13.1(l)(Door Restrictor) x The car door shall be restricted from opening when in the closed position anywhere outside the unlocking zone.
A17.1-2016 : Elevators 1.6 - Car emergency signal 8.6.4.19.15 Emergency Communications x A visual indication on the same panel as the "PHONE" push button shall be provided to acknowledge that two-way communications link has been established.
A17.1-2016 : Elevators 2.4 - Machine space 8.6.4.8 Machine Room and Machinery Space x Pieces of the drop ceiling are missing in the machine room and shall be installed/replaced.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.7.2.15.2 x The illuminated signal for emergency power shall operate as required.
A17.1-2016 : Elevators 1.17 - Standby power operation 8.7.2.16.4 x The car shall run correctly on emergency power. The car ran up to verify the ability to light the load, but would not respond after first run.
A17.1-2016 : Elevators 2.14 - Code data plate 8.9 x A data plate shall be provided indicating the code in effect at the time of the alteration and the applicable requirements of section 8.7.