MO Minimum : Elevators
|
(H) - Machine Rooms
|
(H)2
|
|
|
machine room door needs to be self locking. key operated only from outside
|
6/13/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.3 - Lighting and receptacles
|
2.7.5.1
|
|
|
machine room light switch needs to be inside room next to entry door Currently it in stairway outside room 6 feet from entry door
|
6/13/2025
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
2.6 - Ventilation
|
2.7.5.2
|
|
|
HVAC not working in machine room.
|
10/8/2024
|
ASME A17.1 2004 with 2005 Addendum and 2005 : Elevators
|
1.5 - Car lighting and receptacles
|
8.6.4.15 Emergency Lighting
|
x
|
|
emergency light not working. em bell and phone ok
|
6/23/2025
|